Permit: T01CM01952

Parcel: 105095510


Addresses:

4701 N STONE AV

Inspection Status: Approved

Inspection History: PLUMBING - PROGRESS

Date Description Inspector Results Comments
02/01/2002 PLUMBING - PROGRESS Approved
11/29/2001 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*3/4 SITE WATER ONLY TEST OK OK TO BACKFILL. PLEASE PROVIDE DRAWING ON LOCATION OF 3/4" TIE IN WITH VALVE SEC #1. ON PLAN MEP-1. SEC PLAN MEP-1 WILKINS MODEL MDD975XLMS. LOCATE WIRE FOR SWITCH.
11/28/2001 PLUMBING - PROGRESS Not ready for Inspection IVRS - Inspection 0000*NOT READY ON SITE WATER PLEASE PROVIDE TEST DO NOT COVER.
11/02/2001 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*KIOSAK BLDG COPPER UNDER SLAB OK WRAP IN CONCRET.
11/01/2001 PLUMBING - PROGRESS Partial Approval IVRS - Inspection 0000*PLANS CALL FOR COPPER IN BLDG PARTIAL SITE WATER ONLY TEST A LATER DATE HOPE IT HOLD PRESSURE NOT READY AT BLD.