Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM01952
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL | |
01/29/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NOT READY. | |
01/28/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
01/27/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK POWER FOR TEST CALL JIM MARCH BANKS & TEP 2:40 PM. | |
01/24/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*CANCEL | |
01/20/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) LIGHTPOLE INSPECTION WILL BE REQUIRED 2.) CONTROL PANEL TO BE LISTED AS A MAIN SERVICE DISCONNECTING MEANS 3.) UPS UNIT IS IN THE WORKING CLEARENCE AREA. IT WILL NEED TO BE MOVED 4.) ALL CAPS TO BE REPLACED ON BY FITTING 5.) PLEASE PROVIDE BOND FOR WATER PIPING 250-104. | |
01/18/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
01/16/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) CANOPY ROOF OK SIGN NOT IN 2.) CANOPY OK 3.) ALL DISPENSERS OK, EYS FILLED BUT NEED CAPS PUT BACK ON, DISPENSERS LISTED. 4.) SERVICE EQUIPMENT ROOM LOCKED. 5.) MISSING LIGHT POLE SOUTHEAST CORNER OF LOT. CALL BACK WHEN APPRVD PLAN ON SITE AND EGMT ROOM OPEN. |