Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/18/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*1)P.O.C OF NEW BUILDING DRAIN TO EXSISTING BUILDING DRAIN OK.2)SOIL WATER TEST OK.3)OK FOR BACKFILL. |
| 05/17/2001 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1)APPROVED PLAN CALLS FOR 4" VTR.2)DIRTY ARM FOR WET VENTED LAV. CAN ONLY BE 1 PIPE SIZE LARGER THAN ALLOWED TRAP SIZE.SEE SECTION:1003.3 94 UPC.3)RETEST SYSTEM. |