Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR. | |
11/27/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0225*1.) DO NOT DOUBLE UP ON GROUNDING LUGS. 2.) GROUND OFFSETT NIPPLES AT GUTTER AND BETWEEN SWITCH AND METER CAN. 3.) TIGHTEN LOCKNUT ON GUTTER. |