Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/12/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 06/11/2001 |
FRAMING |
|
Partial Approval |
1) PROVIDE 1" CLEARANCE FROM COMBUSTIBLE MATERIALS AT HOT WATER AND FURNACE FLUE PIPE VENT 2) SECURE ABS AT HALL LAV DRAIN TO 1/4 INCH SLOPE PER FOOT 3) PROVIDE TEST AT TUB AND SHOWER DRAINS, SECURE VALVE 4) SEE SHEARWALL ANCHOR BOLT SCHEDULE 5) SECURE FLAT CABLE STANDING ON EDGE |