Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR POWER NEED TO SEE DURING CROSSOVER CALL OFFICE BETWEEN 6:30 AND 7:15 TO SCHEDULE APPOINTMENT 791-5649 EXT 136 CALLED JUDY 10:58 AM |
| 06/28/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/26/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
1.) NEED BONDING DEVICE BOTHSIDE OF NIPPLE 250-94 AT SERVICE 2.) CLEAN SURFACE UNDER LUG 250-12 3.) CHECK SERVICE BOND TO NEUTRAL 4.) DOUBLE LUGING AT CT CAN 5.) NEED FUSES AS SPECIFIED OR LETTER FROM ENGINER AUTHORIZING USE OF INSTALLED FUSES 6.) CLEAN SURFACE UNDER LUG, LABEL DISCONNECT ROOF A/C |