Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/10/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* RECEIVED TRANSMITTED APRIL 2 2002 REFRIGERANT AT TUCSON HOUSE. THIS WAS NECESSARY BECAUSE CHILLERS IN EXCESS OFF 100 TONS ARE IN SAME EQUIPMENT ROOM AS BOILERS. |
| 04/01/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*NO CALL FROM WHEN CHECKING ALARM FREON SENSING SYSTEM REF. MONITOR. WANT WRITTEN RESULTS AND DATE OF TEST SIGNED BY TECH.. WHO ADMINSTERED TEST THIS SYSTEM ALSO SECURED BOILER OPERATION. |