Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM01876
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
02/11/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) SHEET METAL SCREWS ARE NOT ALLOWED FOR GROUNDING 250-12. STARTER CABINET & DISCONNECTS. 2.) CONDUIT RUNS NOT TO HAVE MORE THAN 360 IN A SINGLE RUN 3.) PLEASE CLEAN SURFACE UNDER LUG 250-8. 4.) PLEASE TIGHTEN LOOSE SEAL TITE FITTNGS 5.) ITEM #7 ON PAGE E-2 ASK FOR OVER LOADS PLEASE VERIFY. 7.) PLEASE PROVIDE A LETTER FROM THE ENGINEER REGARDING BREAKER & SIZE FEEDER RUN TO WC-2 |