Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 02/11/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) SHEET METAL SCREWS ARE NOT ALLOWED FOR GROUNDING 250-12. STARTER CABINET & DISCONNECTS. 2.) CONDUIT RUNS NOT TO HAVE MORE THAN 360 IN A SINGLE RUN 3.) PLEASE CLEAN SURFACE UNDER LUG 250-8. 4.) PLEASE TIGHTEN LOOSE SEAL TITE FITTNGS 5.) ITEM #7 ON PAGE E-2 ASK FOR OVER LOADS PLEASE VERIFY. 7.) PLEASE PROVIDE A LETTER FROM THE ENGINEER REGARDING BREAKER & SIZE FEEDER RUN TO WC-2 |