Permit: T01CM01818

Parcel: 12401008B


Addresses:

1071 N MOUNTAIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/24/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK FINAL.
07/23/2001 ELECTRIC - FINAL Partial Approval 1.) CANNOT STACK LUGS. 2.) CLEAN SURFACE UNDER LUGS 3.) FUSES NOT TO PLANS 4.) FINISH OUTSIDE DISCONNECT.