Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/27/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK ROUGH ELECTRIC SWINIUCH ELECTRIC IS CONTRACTOR ON PROJECT. |
| 09/14/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) ALL BOXES TO BE MADE UP 2.) SUPPORT NM CABLE AS PER CODE. 3.) NEED GROUNDING AT METAL BOXES USE LISTED AND APPROVED GROUNDING CONNECTIONS 4.) REPAIR UNSAFE WIRING CONDITIONS 5.) LOOSE ROMEX CONNECTORS. 6.) FILL UNUSED OPENING IN PANEL 7.) CORRECTLY INSTALL FHA STRAPS FOR FULL CABLE PROTECTION NO FURTHUR INSPECTION UNTIL LICENSED ELECTRICAL CONTRACTOR CONTACTS ME A REFEE WILL BE ISSUED IF NOT COMPLETE ON FURTHER INSPECTIONS. |
| 09/05/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0935*1.) ALL BOXES TO BE MADE UP FOR ROUGH ELECTRIC. 2.) SUPPORT NM CABLE AS PER CODE 336-18. 3.) NEED GROUNDING AT METAL BOXES 4.) REPAIR UNSAFE WIRING CONDITIONS 5.) LOOSE ROMEX CONNECTORS 6.) NEED FHA STRAPS FOR PROTECTION OF CABLES. A REFEE HAS BEEN ASSESSED. |
| 08/12/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) FINISH PREVIOUS INSPECTION REPORT 2.) OVERFILL OF CONDUCTORS AT PANCAKE 3/0 OX 370-16 3.) LOOSE ROMEX CONNECTORS 4.) CIELING BOX TO BE RATED FOR WEIGHT AS PER CODE 370-27. 5.) SECUER ROMEX CABLE TO BOXES AS CODE 370-17-373-5 (C) |
| 07/22/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) FINISH ELECTRICAL MAKE UP 2.) USE APPROVED CONNECTORS FOR BOXES & PANEL 3.) STRAP NM CABLE AS PER CODE. 4.) PROTECT NM CABLE AS PER CODE FHA STRAPS 5.) DRILLED HOLES TO MEET CODE FOR STRUCTURE 6.) VERIFY LICENSED ELECTRICAL CONTRACTOR BEFORE WORK PROCEEDS. |