Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/31/2001 |
BUILDING - FINAL |
|
Approved |
PER INSPECTION CARD PROVIDED BY KB HOME |
| 08/27/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE ACCESS TO BACK WATER VALVE SEE SEC 710.6 1994 UPC. 2.) PROVIDE APPROVED LISTING FOR AS BUILT OR YOU MAY APPEAL TO THE CITY OF TUCSON BUILDING OFFICIAL FOR APPROVAL A.S.A.P. THIS DWELLING WILL REMAIN ON TEMP/POWER AND IS SUBJECT TO TERMINATION. |
| 08/24/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*NO ACCESS TO ATTIC. |
| 08/20/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE UPC 710.6 NOTE #2 ABOVE 2) NOTE #4 ABOVE AS PREVIOUSLY ADVISED 3) CLEARANCE FOR HOT WATER OK PROVIDE WATER HEIGHT PAN UNDER SEE UPC 510.7 REMOVE COMBUSTIBLE MATERIAL FROM UNDER/BEHIND (MANUFACTURERS SPECIFICATIONS) 4) IF THIS INSPECTION IS CALLED IN WITHOUT COMPLIANCE TO ISSURES ADDRESSED A RE-FEE WILL BE IMPOSED |
| 08/16/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NOTES: NUMBERS 4, 7 AND 2 NOT ADDRESSED |
| 08/13/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO ACCESS TO ATTIC INSPECTION 2) BWV NOT ACCESSIBLE 3) IDENTIFY PANEL 4) EAVE VENT OBSTRUCTED BY BAFFLE 5) SOFT STUCCO AT NORTH WALL 6) POST TENSION TAG 7) ACCESS AND WORKING SPARE AT HOT WATER NOT SIZED PER UPC SEC. 511.0, NEEDS TO BE MINIMUM 24 INCHES |