Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/11/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 06/07/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) 1 ROW MISSED IN TNTERIOR-MIDDLE SHEARWALL 1ST FLOOR 2) NEED STUD CLIPS AT BOTTOM OF FRONT COLUMN 3) NEED HORIZONTAL STRAPS ON TOP PLATES AT SEVERAL NON CABIN TIED INTERSECTING WALLS IN FRONT 4) A-35 OR H2.5 PATIO LEDGER 5) TRUSSES OVER FRONT ENTRY ARE NOT 2 POINT BEARING |
| 06/06/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |