Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T01CM01770
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/14/2001 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000*1)SOIL WATER TEST OK. 2)P.O.C. OF NEW BUILDING DRAIN TO EXISTING BUILDING DRAIN OK.3)NOTE:WILL REQUIRE A REVISED AND APPROVED DRAWING ON WASTE AND VENT SYSTEM BEFORE NEXT INSPECTION.4)OK TO BACKFILL TRENCH. |
|
06/12/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*1)GREASE TRAP OUTLET IS 4" PLAN SHOWS 4" WASTE.GREASE TRAP WAS INSTALLED WITH 3" WASTE LINE.THESE CAN BE NO OBSTRUCTION OF FLOW ON OUTLET SIDE OF TRAP.2)VENT FOR GREASE TRAP MUST BE ABOVE CENTER LINE OF DRAIN.3)FLAT VENT FOR P-5 BAR TRI SINK OUTLET OF VENT IS BELOW TRAP.4)RE TEST SYSTEM. |