Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM01740
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* OK FOR C OF O. | |
03/12/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* VENTS ON CONDENSATE DRAIN LINE MUST BE DOWNSTREAM OF TRAPS. LABEL DISCONNECTS ON EVAP. COOLERS OR ON COOLER. PAINT EXPOSED PVC W/LATEX PAINT. | |
02/19/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*1.) PROVIDE CONDENSATE DRAINS FOR AIR HANDLER ON ROOF. 2.) PERMANENTLY LABEL EQUIPMENT ON ROOF. 3.) PROVIDE CONTROL WIRING TO AC EQUIPMENT. 4.) PROVIDE DRAINS FOR EVAP COOLERS 5.) PAINT EXPOSED PVC ON CHILLER W/LATEX PAINT. |