Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/19/2002 |
BUILDING ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 01/09/2002 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*PROVIDE HANGERS WITHIN 8" OF PERIMETER OF SUSPENDED CEILING. |
| 12/13/2001 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 12/12/2001 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 12/10/2001 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 11/27/2001 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 11/20/2001 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) REFRIGERATION CONTROL PANELS NOT TO BE HUNG FROM SPRINKELERS CONDUIT 2.) PLYWOO ABOVE REAR DOOR @ REF. NOT SUPPORTED AT EDGES (NEAR CONDENSER) 3.) CURTIAN WALL NOT KICKED OFF 4.) PROVIDE HANGERS WITHIN 8" OF SUSPENDED CEILING PERIMETER. |
| 11/14/2001 |
BUILDING ABOVE CEILING |
|
Partial Approval |
|
| 11/07/2001 |
BUILDING ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) PROVIDE KICKERS ON "SUSPENDED PARTITIONS" 2.) CHECK SHIM @ BEAM/COL. @ APROX G.1-1 |