Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/11/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/09/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) STRAP SEAL TITE TO WATER HEATER 2.) NEED DISCONNECTING MEANS FOR WATER HEATER 3.) NEED WORKING CLEARENCE IN FRONT OF PANEL 4.) LABELS PANELS 5.) ATTACH FIXTURES TO GRID. 6.) SECURE M/C CABLE WITHIN 12" OF DENTAL LIGHTS. 7.) PLEASE LABEL A/C DISCONNECTS 8.) BOND PULL ENCLOUSER ON ROOF. 9.) LOOSE CONDUIT COUPLING LAST 90 ON ROOF. |