Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM01724
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*PARK OWNER-1)CLEAN DEBRIS OUT OF PEDISTAL.2)COVER ALL UNUSED OPENINGS IN PEDISTAL.3)PROVIDE BUSHINGS AT PEDISTAL SERVICE ENTRANCE FOR 1" CONDUIT ATTACHMENT. 4)PROVIDE PROOF OF GROUNDING ELECTRODE SYSTEM AT PEDISTAL OR INSTALL NEW GROUNDING ELECTRODE SYSTEM.5)REMOVE PAINT UNDER NEW EQUIPMENT GROUNDING LOG AND AFFIX TO CABINET WITH MACHINE BOLT.6)BOND NEUTRAL TO GROUND AND TO GROUNDING ELECTRODE SYSTEM. HOME OWNER-7)ALL OUTLET AND SWITCH PLATES MUST BE IN PLACE.8)INSTALL SMOKE DETECTORS. |