Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/11/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 06/07/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) RETURN AIR DUCTS NOT INSTALLED AS PER PLAN, KITCHEN MISSING SUPPLY DUCT 2) GIRDER NOT INSTALLED AS PER PLAN AS PREVIOUSLY NOTED 3) BLOCK MECHANICAL 3 SIDES COMPLY WITH NOTES OF 06/04/01 OR REFEE WILL BE IMPOSED |
| 06/06/2001 |
FRAMING |
|
Denied |
1) SECURE ROMEX AT FLAT ANGLE 2) PROVIDE DUCT AS PER PLAN AT LIVING ROOM |
| 06/04/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROTECT ROMEX CABLE AT GARAGE, SECURE FLAT CABLE 2) DRAFT STOP AT HALL FURNACE DOWN NOT COMPLETE 3) PROVIDE GIRDER DETAIL CONNECTIONS 6/SD2 POST BLOCK BETWEEN A DOUBLE TOP PLATE 2/SD2 PROTECT FROM LATERAL ROTATION 4) ANCHOR BOLTS GARAGE FRONT 5) PROVIDE SHEAR TRANSFER AT RIGHT SIDE OF SLIDER 6) SEE SHEET 6N NOTE #9 7) DUCTS NOT INSTALLED AS PER PLAN, SEVERAL MISSING 8) HEADER NOT SIZED PER PLAN |