Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/10/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 07/06/2001 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) DONT RUN SEWER TRUNK IN PARALLEL WITH FTG. 2.) DONT USE SANT ON IT BACK VERTICAL POSITION ONLY 3.) KEEP TRAP ARM SAME SIZE (DIA) PIPE FROM VERT DRAIN VENT 4.) LONG SWEEP GOING VERT TO HUTIZ, 1/4 OR HORIZ TO VERT. USE LONG SWEEP LYING FLAT AT 90 TURNS. 5.) FLOOR DRAIN 2" NEEDS TRAP PRIMER, SUGGUST FRENCH DRIAN SEE SKETCH 6.) NEED 2 WAY CLEAN OUT SEE DRAWING. |