Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM01697
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2001 | ELECTRIC - FINAL | Denied | CALL FOR FINAL WHEN BLDG IS ELECTRICALLY POWERED | |
04/12/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1) COKE DISPENSER TO HAVE APPROVED LISTING LABEL 2) LOOSE CONDUIT FITTINGS INSIDE AND OUT 3) SUPPORT CONDUIT AS PER CODE INSIDE AND OUT 4) EXPOSED ROMEX 5) WORKING CLEARANCES IN FRONT OF SUB PANEL 6) INSTALL OUTSIDE LIGHTS AS PER CODE 7) SERVICE IN POOR CONDITION-REPAIR OR REPLACE AS NECESSARY 8) CONDUIT ON ROOF? 9) PROPER WIRING METHODS AND EQUIPMENT NEEDED ON ROOF 10) NEED TO HAVE LICENCED L-11 ELEC. CONTRACTOR PERFORM WORK |