Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
|
| 07/18/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) SUPPORT J-BOXES TO STRUCTURE 370-23 N.E.C. 2.) SUPPORT MC CABLE WITHIN 12" EACH TERMINATION, THE ONLY EXCEPTION ARE 6' FIXTURE WHIPS. 334-10 N.E.C. 3.) MUST HANG OWN CEILING WIRES FOR SUPPORT. DON NOT USE CEILING WIRES INTENDED TO SUPPORT GRID. 300-11 N.E.C. 4.) SUPPORT EMT WITHIN 3' EACH BOX PER ART 348-13 N.E.C. |