Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 08/02/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 07/31/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NEED SIMPSON EQUIVALENT HANGER GARAGE (INSTALLED ADVANCE TYP HGUS 5 25/10 REQUIRE COMMON NAILS, HARDWARE FOR POST TO BEAM NOT ON PLAN 2) EXHAUST FAN DAMPERS TAPED WON'T OPEN 3) 8 TECO NAILS USED IN GARAGE BEAM HANGER USE 16 COMMON, NOT SINKERS 4) SPARK PLATE FIREPLACE 5) ADD STUDS AT 2ND FLOOR FURNACE COMBUSTIBLE DUCT 6) 2ND FLOOR EXHAUST FAN DUCT NOT ATTACHED 6) GAS TEST OK |