Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/26/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR FOR TEMP POWER |
| 02/22/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*CONTRACTOR NOT ON SITE. NOTE THAT NEW SERVICE SWITCHGEAR HAS BEEN ENERGIZED BY THE ELECTRICAL CONTRACTOR PRIOR TO CITY INSPECTORS APPROVAL. UPON TEP INSPECTION, GREG CARTER FOUND EXPOSED SECONDARY FEEDERS ENERGIZED AND EXPOSED TO THE PUBLIC.IT APPEARS THE NEW GREAR WAS ENERGIZED OR BACK FED FROM AN EXISTING SERVICE ON PREMISES. SWITCH GEAR STILL ENERGIZED LOCKED DOORS, TEP LOCKS. PLEASE CALL STEVE LONG, CITY OF TUCSON INSPECTION MANAGER 791-5550. |
| 11/14/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*PLEASE COMPLETE FORM FOR TEMP POWER FOR TESTING AND RECALL FINAL |