Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01CM01619
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2002 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*1.) NO BOND POSTED FOR ELECTRIC TEST & POWER. | |
| 05/17/2002 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000*CANCELLED PER TOM WITH ELECT. | |
| 05/14/2002 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000*NOTES 1.) WATER BOND TO BE SIZE PER TABLE 250-66. ALSO SEE ONE LINE DIAGRAM ELECT. PLAN. 2.) STEEL CONDUIT RACEWAY FOR WATER BOND JUMPER MUST HAVE BONDING BUSHING PER 250-64E. 3.) BOND BUSHINGS IN CT OR TERM. CANO F SERVICE MUST BE BONDED TO ENCLOSURE. 4.) CLOSE NIPPLE BETWEEN PANELS IN ELECT ROOM TO HAVE LOCKNUTS BOTH INSIDE & OUTSIDE OF ENCLOSURE. | |
| 05/09/2002 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000*NOTES 1.) INSTALL MAIN BONDING JUMPER FOR NEUTRAL 2.) BOND WATER PIPING PER NEC & PLAN 3.) PLANS NEED TO BE REVISED TO REFLECT FIELD INSTALLATION, APPROVED THRU PLAN CHECK. 4.) UFER WAS NOT INSPECTED, EXPOSED FOR INSPECTION. | |
| 04/15/2002 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection 0000*OK U.G. SECONDARYS. |