Inspection Status: Denied
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 05/20/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*1.) NO BOND POSTED FOR ELECTRIC TEST & POWER. |
| 05/17/2002 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000*CANCELLED PER TOM WITH ELECT. |
| 05/14/2002 |
ELECTRIC - CABLE DROP |
|
Partial Approval |
IVRS - Inspection 0000*NOTES 1.) WATER BOND TO BE SIZE PER TABLE 250-66. ALSO SEE ONE LINE DIAGRAM ELECT. PLAN. 2.) STEEL CONDUIT RACEWAY FOR WATER BOND JUMPER MUST HAVE BONDING BUSHING PER 250-64E. 3.) BOND BUSHINGS IN CT OR TERM. CANO F SERVICE MUST BE BONDED TO ENCLOSURE. 4.) CLOSE NIPPLE BETWEEN PANELS IN ELECT ROOM TO HAVE LOCKNUTS BOTH INSIDE & OUTSIDE OF ENCLOSURE. |
| 05/09/2002 |
ELECTRIC - CABLE DROP |
|
Partial Approval |
IVRS - Inspection 0000*NOTES 1.) INSTALL MAIN BONDING JUMPER FOR NEUTRAL 2.) BOND WATER PIPING PER NEC & PLAN 3.) PLANS NEED TO BE REVISED TO REFLECT FIELD INSTALLATION, APPROVED THRU PLAN CHECK. 4.) UFER WAS NOT INSPECTED, EXPOSED FOR INSPECTION. |
| 04/15/2002 |
ELECTRIC - CABLE DROP |
|
Partial Approval |
IVRS - Inspection 0000*OK U.G. SECONDARYS. |