Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/21/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 03/17/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) SUPPORT WIRE IS NEEDED FOR EXIT SIGNS. 2.) MISSING JUNCTION BOX COVERS 3.) CONDUIT RUNS NOT ALLOWED MORE THAN 360 IN A RUN. 4.) FILL ALL UNUSED OPENING IN JUNCTION BOX. |
| 03/07/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245*1.) PLUG UNUSED OPENING IN J-BOX 2.) SOME J-BOXES OVERFILLED FOR #OF CONDUCTORS, CHECK ART 370-16A N.E.C. 3.) COMPLETE MAKE UP IN J-BOXES. 4.) CONDUITS TO BE SECURLY FASTENDED TO STRUCTURE WITHIN 3' EACH BOX PER ART 348 N.E.C. 5.) APPROVED PLANS TO BE ON SITE. |