Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
01/08/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PLEASE PROVIDE LETTER VERIFYING TORQUE VALVES AT SERVICE 2.) FILL UNUSED OPENINGS AT PANEL 3.) PROVIDE CIRCUIT DIRECTORY. 4.) BONDING JUMPERS TO BE SIZED AS PER CODE 250-102. 5.) GUTTER WITH CT CAN TO BE LOCKABLE OR SEALABLE PER TEP. |