Permit: T01CM01610

Parcel: 10304001J

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM01610

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/14/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
01/08/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE PROVIDE LETTER VERIFYING TORQUE VALVES AT SERVICE 2.) FILL UNUSED OPENINGS AT PANEL 3.) PROVIDE CIRCUIT DIRECTORY. 4.) BONDING JUMPERS TO BE SIZED AS PER CODE 250-102. 5.) GUTTER WITH CT CAN TO BE LOCKABLE OR SEALABLE PER TEP.