Permit: T01CM01591

Parcel: 11613195F

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/28/2001 ELECTRIC - FINAL Approved PER RICK HOLLAND AND STEVE LONG.
11/14/2001 ELECTRIC - FINAL Partial Approval OK ELECTRIC SUBJECT TO OTHER INSPECTION OK TEMP C OF O SUBJECT TO OTHER INSPECTION.
11/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) PROVIDE LETTER VERIFYING TORQUE OF SERVICE EQUIPMENT 2.) NEED TO SEE MANUFACTURES INSTALLATION PAPERWORK FOR SERVICE 3.) LABEL A/C DISCONNECTS & TIGHTEN & STRAP SEALITITE 3.) EXPOSED CONDUCTORS AT FUTURE CHAIR LIGHTS. 5.) WORKING CLEARANCE INFRONT OF WATER HEATER DISCONNECT 6.) FILL UNUSED OPENINGS I PANEL #1. 7.) LABEL PANEL ON OUTSIDE OF COVER 8.) CONDUIT RUNS NOT TO HAVE MORE THAN 360 IN BENDS 9.) SUPPORT M/C CABLE AT FLO -SAFE MANIFOLD 10.) PROTECT CABLE AT CONDUIT END.
11/08/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK FOR TEMP SERVICE FOR TESTING SUBJECT TO OTHER INSPECTIONS.