Permit: T01CM01585

Parcel: 10510010D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM01585

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2001 ELECTRIC - ABOVE CEILING Approved
05/07/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* WEST WING: 1) CONDENSATE TO BE IN COMPLET RACEWAY SYSTEM 2) INDEPENDANT SUPPORT OF ELEC. CAN NOT USE CEILING SUPPORT WIRES 300-11 HALL: 3) SUPPORT FIXTURES 4) SUPPORT MC CABLE AS PER CODE 334-10
05/02/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
04/25/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* 2 TRAINING ROOMS, 1 DATA ROOM, AND 1 PAYROLL ROOM
04/24/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000* TRAINING ROOM 1 & 2:
1) WORKING CLEARANCES A/C DISCONNECTS
2) ATTACH FIXTURES TO GRID 3) SUPPORT DATA ON INDENPENDANT SUPPORT WIRES 4) SUPPORT CONDUIT AS PER CODE 5) SUPPORTS TO BE AS PER 300-11 ALSO 6) FINISH BOXES MAKE UP