Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM01585
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2001 | ELECTRIC - ABOVE CEILING | Approved | ||
| 05/07/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* WEST WING: 1) CONDENSATE TO BE IN COMPLET RACEWAY SYSTEM 2) INDEPENDANT SUPPORT OF ELEC. CAN NOT USE CEILING SUPPORT WIRES 300-11 HALL: 3) SUPPORT FIXTURES 4) SUPPORT MC CABLE AS PER CODE 334-10 | |
| 05/02/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
| 04/25/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* 2 TRAINING ROOMS, 1 DATA ROOM, AND 1 PAYROLL ROOM | |
| 04/24/2001 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* TRAINING ROOM 1 & 2: 1) WORKING CLEARANCES A/C DISCONNECTS 2) ATTACH FIXTURES TO GRID 3) SUPPORT DATA ON INDENPENDANT SUPPORT WIRES 4) SUPPORT CONDUIT AS PER CODE 5) SUPPORTS TO BE AS PER 300-11 ALSO 6) FINISH BOXES MAKE UP |