Permit: T01CM01583

Parcel: 123051870


Addresses:

2401 E ELM ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/11/2001 FRAMING Approved IVRS - Inspection 0000*
11/28/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) GROUND ALL METAL ELECTRIC BOXES 2) PROVIDE PIG TAIL GROUNDS FOR ALL SWITCHES 3) BREAK THRU NOT MADE 4) MAKE UP ALL GROUNDS 5) FLOOR DRAIN REQUIRES A TRAP PRIMER 6) DRAFT STOP DROP CEILING FAN 7) GAS LINE MUST BE ELECTRICALLY BONDED 8) NAIL PROTECT WIRES WITHIN 1 1/4" OF SURFACE 9) BLOCK DEFUSER BOOTS 3 SIDES