Inspection Status: Closed
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/11/2008 |
ELECTRIC - INTERMEDIATE |
|
Closed |
|
| 08/07/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK SECTIONS 1 & 2 OF MAIN SWITCH BOARD OK SWITCH BOARD "A/C" 1.) NEED LETTER VERIFYING TORQUE SETING 2.) NEED LETTER FROM ENGINEER REGARDING 2-350 AL TO 1-500 CU TAPS 3.) NEED INFO AS TO EQUAL FOR BREAKERS. |
| 05/20/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK 3-4" AND 1-2 1/2" PVC SRS EXISTING SERVICE.OK PVC CONDUIT RUNS THROUGH ATTIC TO PANELS.OK 500 MCM BOND WIRE WITH TRENCH. |