Permit: T01CM01579

Parcel: 115180050


Addresses:

1601 N ORACLE RD

Inspection Status: Closed

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/11/2008 ELECTRIC - INTERMEDIATE Closed
08/07/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK SECTIONS 1 & 2 OF MAIN SWITCH BOARD OK SWITCH BOARD "A/C" 1.) NEED LETTER VERIFYING TORQUE SETING 2.) NEED LETTER FROM ENGINEER REGARDING 2-350 AL TO 1-500 CU TAPS 3.) NEED INFO AS TO EQUAL FOR BREAKERS.
05/20/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK 3-4" AND 1-2 1/2" PVC SRS EXISTING SERVICE.OK PVC CONDUIT RUNS THROUGH ATTIC TO PANELS.OK 500 MCM BOND WIRE WITH TRENCH.