Permit: T01CM01578

Parcel: 138232460


Addresses:

621 W INEZ PL

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/28/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*/ 1) GAS LINE AND WATER HEATER WILL BE INSPECTED BY OTHERS
09/14/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) CLEARANCE FOR WATER HEATER REMOVAL NOT PROVIDED 2) TPRV NOT INSTALLED PER CODE, CHANGE
09/06/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) GFCI OUTLETS AT KITCHEN 2) PRE RELIEF VALVE CONDENSATE LINE MUST RUN DOWN TO SIDE OF HOUSE 2' MINIMUM HIGH FROM GROUND 3) SECURE GAS LINE AT UTILITY ROOM 4) PROVIDE BONDING AT GAS LINE AND WATER
08/21/2001 BUILDING - FINAL Denied 1) ADDRESS NOT VISIBLE FROM STREET 2) IDENTIFY ADDRESS AT METER SOCKET 3) PROVIDE ALL LIGHT FIXTURES RECEP AND SWITCH PROTECTIVE COVERS 4) SECURE FLUE PIPE AT HOTWATER 5) IDENTIFY LOCATION OF TEMPERATURE RELIEF VALVE DRAIN AT HOTWATER 6) PROVIDE BOND WIRE TO GAS AND WATER PIPE ACCESSIBLE LOCATION 7) PROVIDE INSIDE DOOR LOCKS THAT DON'T REQUIRE KEY TO OPEN 8) PROVIDE 10 PSI MINIMUM FOR GAS PRESSURE TEST