Permit: T01CM01575

Parcel: 137115910


Addresses:

1471 W RUHE PL

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
06/12/2001 FRAMING Approved IVRS - Inspection 0000*
06/05/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) PROVIDE TRIMMERS UNDER HEADERS 2) PROVIDE CRIPPLES UNDER DOUBLE TOP PLATE 3) SECURE HEADER WITH 16D NAILS INSTALL PLYWOOD BETWEEN 4) REMOVE SCREWS USE TICO'S NAILS 5) ELECTRIC METALLIC TUBING NEEDS TO BE BONDED WITH JUMPER TO GROUND BAR
06/01/2001 FRAMING Not ready for Inspection
05/09/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) SITE PLAN DOES NOT MATCH EXISTING BLDG 2) EXPOSE ELECTRIC ROMEX CABLE AND SECURE 4 FEET 6 INCHES ON CENTER AND WITHIN 10 INCHES OF BOX 3) EXPOSE HEADER AT WEST DOOR 4) IDENTIFY ALL BREAKERS AT PANEL PLUG, KNOCK OUT AT MISSING BREAKER 5) PROVIDE DEEP BOX FOR CEILING FAN IN NEW PLAY ROOM