Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/21/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/19/2001 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) EXTERIOR GFCI WILL NOT TRIP 2) 2 EACH HOSE BIBS MISSING VACUMN BREAKERS (#3 NOTE) 3) #6 NOTE DATED 9/13/01 4) SHET OFF VALVE AT GAS LINE BEHIND STOVE 5) #5 INSTALL ANTI-TIP AT STOVE 6) IDENTIFY AND PROTECT LOOSE WIRES |
| 09/13/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) 3252 ADDRESS MUST BE ON HOUSE IN 3" HIGH NUMBERS VISABLE FROM THE STREET 2) NO POWER ON HOUSE 3) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 4) WATER HEATER VENT MUST EXTEND 1 FOOT HIGHER THAN VERTICAL WALL WITHIN 4 FEET MINIMUM HEIGHT 5 FEET 5) PROTECT NMC WIRE BELOW 8' 6) WATER HEATER REQUIRES COMBUSTION AIR PER CODE 7) WASTE VENT CANNOT BE DRILLED FOR CONDENSATE CONNECTION 8) ROOF A/C WEATHER TIGHT CONNECTIONS LOOSE 9) A/C NOT LEVEL 10) A/C DISCONNECT OBSTRUCTED BY UNIT MUST HAVE 30" X 30" UNOBSTRUCTED WORK AREA IN FRONT 11) STOPPED INSPECTION TO MANY ITEMS 12) NEXT FAILURE WILL BE CHARGED A RE-INSPECTION FEE |
| 09/05/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0950*/ 1) NOT COMPLETE ENOUGH TO INSPECT, THE HOUSE MUST BE COMPLETE AND READY FOR OCCUPANCY PRIOR TO FINAL INSPECTION |