Permit: T01CM01527

Parcel: 108213260

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T01CM01527

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2001 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*ABOVE CEILING OK ABOVE CEILING.
07/05/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0935*1.) DATA LAYING ON TILE 2.) M/C CABLE WITH NO JUNCTION BOX OR GAP LAYING HARD CEILING ENTRY.3.) A REFER HAS BEEN ACCESSED.
06/05/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1)USE APPROVED FITTINGZ AND PARTS FOR CONNECTION TO FLOOR BOXES-
ALL BOXES.2)LOOSE FITTINGS AND SUPORT SEALTITE TO FURNITURE.3)MOVE RECEPTACLE FROM BEHIND SINK.4)CABLE COAX SYSTEM TO BE PLENUM RATED.5)NEED WORKING CLEARANCE A/C UNIT FC-9.
06/04/2001 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*2ND FLOOR OCCUPIED WITHOUT INSPECTIONS-IN C OF O OR FINAL INSPECTIONS.NOT TO BE OCCUPIED WOTH OUT CLEARANCES.1)WORK CLEARANCE IN FRONT OF A/C
DISCONNECT IN LOBBY.2)SUPPORT M/C PER CODE.
3)DATA WIRE LAYING ON GRID.
05/29/2001 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK 2ND FLOOR ABOVE CEILING.