Permit: T01CM01522

Parcel: 13421084A


Addresses:

6992 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/18/2002 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection 0000*LABEL UNITS DISCONNECTS PERMANENTLY.NO INK STILL NEED TO SEE DIFFUSERS NOT INSTALLED ON 1ST FLOOR.
01/14/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*3 DIFFUSERS NOT CONNECTED TO FLEX DUCT. PROVIDE OUTSIDE AIR VENTS. PAINT EXPOSED PVC W/ LATEX PAINT. IDENTIFY CIRCUITS & UNIT NUMBERS ON ELEC. DISCONNECT REDWOOD SLEEPERS ON 1 AC UNIT ARE PARRELLEL TO ROOF JOISTS-SLEEPERS MUST SPAN JOISTS.
12/12/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
11/05/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) A/C UNITS ON ROOF DO NOT HAVE ADEQUATE CLEARANCE FOR SERVICE. SEE MANUFACTURERS INSTRUCTIONS FOR PROPER CLEARANCE. 2.) PROVIDE FLEXIBLE CONNECTORS ON DUCT TO A/C UNIT COVER WITH SUN SHIELD. 3.) PROVIDE OUTSIDE AIR VENTS AS PER PLANS 4.) INSTALL EXHAUST DUCT IN 2ND FLOOR MENS ROOM OK TO SHEET ROCK ALL OTHER REST ROOM NEED DIRECTIONS FROM ARCHITECT ON FIRE DAMPER LOCATIONS. UNITS ON ROOF NOT MODEL SHOWN ON PLANS. PROVIDE APPROVED FROM ARCHITECT. OK TO INSTALL GRID CEILINGS.
09/25/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) SUPPLY RETURN AIR DUCTS, IN CHASES, OK 1ST FLR. UP THRU ROOF. 2.) NOTE ALL SUPPLY RETURN SHT. MTH. FITTINGS NEED TO BE WRAPED.
08/30/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*DUCTED RETURNS CHASES ON 2ND FLR. ARE NOT PLENIUMS.