Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/20/2001 |
ELECTRIC - FINAL |
|
Approved |
|
| 07/09/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PREVIOUSLY APPROVED. |
| 07/06/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 07/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*TEMP POWER 1.) ALL MAIN DISCONNECTING MEANS ARE REQUIRED TO CONNECT NEUTRAL TO ENCLOSURE (GREEN SCREW) THUR NEUTRAL BLOCK OR JUMPER.2.) INSTALL REJECT PINS ON FUSE HOLDER. 3.) NEUTRAL BAR TYING GROUND BAR TO BE REMOVED IN SUBPANEL REMOVE GREEN SCREW ON NEUTRAL SIDE. |