Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2001 | ELECTRIC - INTERMEDIATE | Approved | ||
| 06/21/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 06/20/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* SEATING AREA- 1) MC CABLE TO BE SUPPORTED WITHIN 12'' EACH BOX, PER 334 NEC 2) MC CABLE MUST HAVE LISTED CONNECTORS ON ALL BOX TERMINATIONS 110-NEC KITCHEN- 1) INSTALL PLASTIC BUSHINGS PROVIDED WITH MC CABLE TO PROTECT CONDUCTORS FROM ABRASION 300-16 300-15-C NEC 2) MC TO BE SUPPORTED PER ART 334 NEC |