Inspection History Details
Permit: T01CM01500
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2001 | ELECTRIC - INTERMEDIATE | Approved | ||
| 06/13/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
| 06/12/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 06/09/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1)LOOSE FITTINGS AT OWNERS PANEL.2)NEED TO SECURE IN PLACE APPROVED FOR BACK FEED DEVICE.3)LABEL BREAKERS IN OWNERS PANEL.4)LOOSE FITTINGS AT PANEL #113,111,101 AND ON JUNCTION BOXES. 5)FHA STRAPS ABOVE PANEL AND STUDS.FINISH PREVIOUS INSPECTION REQUEST. |
|
| 05/21/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 05/21/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1)NEED BONDING DEVICE ON RISER.2)CLEAN SURFACE UNDER LUG FOR GROUNDS.3)NEED BONDING DEVICES BOTHSIDES OF SERVICE NIPPLE.4)NEED BONDING DEVICES ON OFF SET NIPPLES.5)BOND ENCLOSERS-GUTTER/METERS/DISCONNECTS. 6)NEED GAS AND WATER BONDS.7)NEED REVISED PLANS TO REFLECT WORK DONE ON SITE.8)HAVE PERMIT COUNTER ADD ALL NEEDED INSPECTIONS CABLE DROP,TEMP SERVICE (IF APPLICABLE),FINAL. |