Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/27/2001 ELECTRIC - INTERMEDIATE Approved
06/13/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
06/12/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
06/09/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1)LOOSE FITTINGS AT OWNERS PANEL.2)NEED TO SECURE IN PLACE APPROVED FOR BACK FEED DEVICE.3)LABEL BREAKERS IN OWNERS PANEL.4)LOOSE FITTINGS AT PANEL #113,111,101 AND ON JUNCTION BOXES.
5)FHA STRAPS ABOVE PANEL AND STUDS.FINISH PREVIOUS INSPECTION REQUEST.
05/21/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
05/21/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1)NEED BONDING DEVICE ON
RISER.2)CLEAN SURFACE UNDER LUG FOR GROUNDS.3)NEED BONDING DEVICES BOTHSIDES OF
SERVICE NIPPLE.4)NEED BONDING DEVICES ON OFF SET NIPPLES.5)BOND ENCLOSERS-GUTTER/METERS/DISCONNECTS.
6)NEED GAS AND WATER BONDS.7)NEED REVISED
PLANS TO REFLECT WORK DONE ON SITE.8)HAVE PERMIT COUNTER ADD ALL NEEDED INSPECTIONS
CABLE DROP,TEMP SERVICE (IF APPLICABLE),FINAL.