Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T01CM01497
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2001 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000*1.) 60# AIR TEST OK 2.) REMOVE WATER FROM TRENCH, AND BED GAS PIPE WITH APPROVED CLEAN FILL.3.) DONT FORGET, PRESSURE REGULATORS NEED TO BE TAGGED, AND REGULATOR VENT OPENING NEEDS TO BE PROTECTED AGAINST WATER AND OTHER CONTAMINANTS 4.) OK TO BACKFILL TRENCH. | |
08/16/2001 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) MEDIUM PRESSURE GAS REQUIRES 60# TEST FOR 30 MINUTES 2.) TEST PRESSURES BETWEEN 10# - 100# REQUIRE A GUAGE THAT DENOTES ONE POUND INCREMENTS OR LESS. |