Permit: T01CM01497

Parcel: 13704135E


Addresses:

5505 S NOGALES HY


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T01CM01497

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/19/2001 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*1.) 60# AIR TEST OK 2.) REMOVE WATER FROM TRENCH, AND BED GAS PIPE WITH APPROVED CLEAN FILL.3.) DONT FORGET, PRESSURE REGULATORS NEED TO BE TAGGED, AND REGULATOR VENT OPENING NEEDS TO BE PROTECTED AGAINST WATER AND OTHER CONTAMINANTS 4.) OK TO BACKFILL TRENCH.
08/16/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) MEDIUM PRESSURE GAS REQUIRES 60# TEST FOR 30 MINUTES 2.) TEST PRESSURES BETWEEN 10# - 100# REQUIRE A GUAGE THAT DENOTES ONE POUND INCREMENTS OR LESS.