Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM01497
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2002 | ELECTRIC - INTERMEDIATE | Approved | ||
11/05/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*FINAL ON: SBS SPRAY BOOTH OUTDOOR EAST APPROVED. PAINT MIX ROOM FINAL APPROVED. | |
11/04/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*TO INSPECT 11/5/02 CALL CONTRACTOR. | |
06/24/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*2 OF 3 PAINT MIXER APPROVED NEW T R AND PANEL R-9 APPROVED. | |
06/04/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*APPROVED FOR SPRAY BOOTH NORTH. | |
05/07/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PARTIAL APPROVAL 1.) NEW AIR COMPRESSOR FINAL APPROVED PANEL R-8; 1-3 AND 5. | |
04/29/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | FUTURE SPRAY BOOTH. P-8 TO SHOW CHANGES FOR FINAL. R-8-150 AMP MAIN NEEDED ALSO TO SHOW CHANGE T-8 OK. | |
03/20/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*CORD DROPS FOR PORTABLE EQUIPMENT APPROVED IN FUTURE WILL NEED ENGINEER PLAN, DESCRIPTION AND STAMP. | |
03/10/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*GROUNDING ELECTROD SYSTEM FOR PANEL P-8. | |
02/27/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*FINAL FOR PRO 4002051603 THE 2 BLOWER COLLECTOR MOTORS. FINAL APPROVED. FIND AN PAINT MIX ROOM DENIED EXHAUST FAN MUST BE LISTED EXPLAIN PROOF FOR AREA AND MATERIAL FOLLOW ANY LISTING INSTRUCTION. | |
02/13/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*3 INTERIOR SPRAY BOOTH AND ASSOCIATED EQUIPMENT ON OUTSIDE APPROVED. EQUIPMENT APPROVED LOGIXX OK TO ENERGIZE. ACCUSHEAR, CIRCUITS P2-5.7 AND 9 APPROVED OK TO ENGERIZE AUTOBRAKE, CIRCUIT R5-10,12, AND 14 APRPOVED OK TO ENERGIZE. | |
02/11/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*3 SPRAY BOOTH @ INTERIOR SBS AND ASSOCIATED EQUIPMENT APPROVED. SUBJECT TO OBTAINING MECH. PLUMBING AND BUILDING PERMIT WITH FINALS. CIRCUITS P-6 2,4,6 P68,10,12 P614,16,18. | |
01/24/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*COMPRESSOR ROOM AND DRYER AND ASSOCIATED EQUIPMENT FINAL APPROVED PARTIAL AN DRYER COLLECTOR MOTOR. | |
01/02/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*CTD SAW P-2 PANEL 2-4 & 6 CIRCUIT 8,10 & 12. DORRINGE COLT SAW PANEL P-6 7,9 & 11 APPROVED FOR USEAGE. COMPRESSOR EQUIPMENT IN VIOLATION OF 110-26. AIR LINER IN FRONT OF EQUIPMENT AND NEED LISTING FOR DRYER. MULTI NEEDS LISTING. | |
12/28/2001 | ELECTRIC - INTERMEDIATE | Denied | 1.) THE AIR LINE BELOW THE DISCONNECTS FOR THE COMPRESSOR IS IN THE WORKING SPACE AS PER CODE 110-26. | |
12/27/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*NOTE VERIFY LISTINGS FOR COMPRESSORS & AIR DRYERS & EQUIPMENT OK DEVICES ON INTERIOR PERIMETER WALLS AND COLUMNS. | |
11/26/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*ABOVE CEILING 2ND FL. | |
11/21/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | PLANT IS CLOSED. UNABLE TO INSPECT RAY M. | |
11/20/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*2ND FLOOR ABOVE CEILING. | |
11/16/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PARTIAL 1ST FLOOR OK TO COVER OFFICES. | |
10/17/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*A REINSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION 1.) NEED COMPLETE AND ACCURATE CITY APPROVED CHANGE FOR MIX ROOM. TYPE OF FIXTURE, NUMBER OF FIXTURE VOLTAGE. 2.) MIX ROOM IS CLASSIFIED WILL NEED SEAL OFF AND EXPLAIN PROOF DEVICE, BOXER AROUND DOOR PERIMETA, EXHAUST FAN ETC. ALL EXISTING PILOT DEVICER TO BE INCLUDED. | |
10/08/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) REVISED PLAN ON SITE 2ND FLOOR WALL ROUGH IN OK 2.) 1ST FLOOR BATHROOMS RECESSED LITE FIXTURES OK. | |
09/25/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | BROCKETT ELECTRIC INTER & UNDERGROUND FOR COND. UNITS PARTIAL OK U.G. PAR ON INTER. | |
09/07/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*CALLED ON WRONG PERMIT NUMBER. | |
08/10/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) OK TO RE ENERGIZE UPGRADED SERVICE ONLY TO REENERGIZE EXISTING PORCH L, P-2 AND P-3 DO NOT ENERGIZE ANY OTHER EQUIPMENT/ELECTRICAL NOTE LETTER OF TORQUING RECEIVED WILL NEED GFI TEST PIR N.E.C. STANDARDS PRIOR TO ENERGIZING OTHER PANELS TO INCLUDED BOND POSTING AND OTHER INSPECTORS APPROVED. 2.) PANEL P-6 COMPLETE OK TO COVER & TRANSFORMER. T-6 | |
07/26/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* FEEDER CONDUITS P-8 SECONDARY CONDUIT (8) 4" PVC CONDUITS. | |
07/23/2001 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - Ri canceled |