Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM01492
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/04/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL | |
07/02/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) INSTALL EMEGENCY/BALLAST AS PER MANUFACTURS INSTRUCTIONS NEED TEST BUTTON 2.) USE CORRECT BREAKER FOR INSTALLTION PANEL "A' 3.) LOOSE FITTINGS AT A/C VENT 3.) A REFER WILL BE IF WORK DOES NOT STANDARDS.4.) SEAL DETERIOCATED NOT WEATHER PROOF PLANS SHOW NEW. | |
07/01/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) CHECK PANEL "A" 2.) FINISH EMERGENCY LIGHTING | |
06/28/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) CORRECT PANEL SCHEDULE 2.) DATA LAYING ON GRID SUPPORT AS PER CODE 3.) NEED REVISED PLANS FOR PANEL "A" APPROVED BY CITY 4.) NEED EXTENDER RING TO PROTECT FROM COMBUSTIBLES 5.) MISSING JUNCTION BOX COVERS 6.) FINISH RECEPTACLES 7.) EMG LIGHTING NOT AS PLANS. |