Permit: T01CM01491

Parcel: 105102430

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM01491

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2001 ELECTRIC - INTERMEDIATE Approved
06/12/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*LOCKED NO ACCESS 2:40 P.M.
06/04/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
06/01/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TEMP POWER BOND POSTED.CHECK BONDING CONDUCTOR SIZES.
05/30/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1)DERATE OR PROVIDE CALCULATION FOR CONDUCTORS RUN TO FULL CYCLE.2)SUPPORT CONDUIT-4",3", 2".3)NEED TO KNOW WHAT RATING IS-NOT ON PLANS.4)NEED ADDRESS LABELS.5)NEED TO VERIFY POSTING OF BOND FOR TEMP POWER AND TESTING.
05/29/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
05/16/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK FRONT WALL
05/09/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK SOFFIT FRONT
05/08/2001 ELECTRIC - INTERMEDIATE Partial Approval 1) NEED PHYSICAL PROTECTION FOR AUDIO CABLES-FHA STRAPS 2) USE LISTED RACEWAY FOR V/D/V CABLES 640-9 (A) (I), 640-23(B)
OK WALL ROOM #11-14 AS MARKED ON PLAN,
OK UNDER GROUND ELECTRIC TO SALES OFFICE AND CASHIER UNDER FLOOR
05/04/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK ROOMS 2-5, 8,9 AS MARKED ONSITE PLAN
05/03/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*LOCKED NO ACCESS 2:40 P.M.