Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM01491
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/11/2001 | ELECTRIC - INTERMEDIATE | Approved | ||
06/12/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0920*LOCKED NO ACCESS 2:40 P.M. | |
06/04/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
06/01/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK TEMP POWER BOND POSTED.CHECK BONDING CONDUCTOR SIZES. | |
05/30/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1)DERATE OR PROVIDE CALCULATION FOR CONDUCTORS RUN TO FULL CYCLE.2)SUPPORT CONDUIT-4",3", 2".3)NEED TO KNOW WHAT RATING IS-NOT ON PLANS.4)NEED ADDRESS LABELS.5)NEED TO VERIFY POSTING OF BOND FOR TEMP POWER AND TESTING. | |
05/29/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
05/16/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK FRONT WALL | |
05/09/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK SOFFIT FRONT | |
05/08/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | 1) NEED PHYSICAL PROTECTION FOR AUDIO CABLES-FHA STRAPS 2) USE LISTED RACEWAY FOR V/D/V CABLES 640-9 (A) (I), 640-23(B) OK WALL ROOM #11-14 AS MARKED ON PLAN, OK UNDER GROUND ELECTRIC TO SALES OFFICE AND CASHIER UNDER FLOOR |
|
05/04/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK ROOMS 2-5, 8,9 AS MARKED ONSITE PLAN | |
05/03/2001 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*LOCKED NO ACCESS 2:40 P.M. |