Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T01CM01467
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/25/2001 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection 0000* REMEMBER A VENT MUST BE RUN LEVEL OR SO PITCHED TO DRAIN BACK TO THE FIXTURE IT SERVES | |
04/24/2001 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection 0999* 1) ELEC. WIRE NOT APPROVED STRAPPING MATERIAL ON COPPER 2) BLOCKS OF SHEET ROCK AND SHIM NOT APPROVED FOR VENT SUPPORT |
|
04/17/2001 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection 0999*1. ISOLATE COPPER WHERE TOUCHING EITHER COPPER OR DISSIMILAR METALS.2.CORRECT BACKK PITCH ON OVER HEAD N/H 3. OK TO COVER WALLS 4. TIE-IN IN BASEMENT OK. | |
04/13/2001 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection 0999* |