Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T01CM01452
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/13/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
08/09/2001 | FRAMING | Not ready for Inspection | 1) NEED THE LIST OF REJECTIONS FROM LAST INSPECTION | |
08/08/2001 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) TIGHTEN A.D. NUTS 2) SECURE F/PLACE FLUE FIRE STOP 3) CLEAN OUT ALL COMBUSTIBLE TRASH AROUND F/P CHASE 4) TUB BACKING 5) ADD SCREWS TO REAR HIP JACK TO GIRDER 6) EXPOSE AT EXTERIOR TOW P.A.'S NORTH OF KITCHEN WINDOWS A PORTION OF THE STRAP 7) BATHROOM CIEILING DROPPED BELOWN LIGHTS AND DUCT 8) ADD SCREWS X BRACING AAT CHANNEL 9) SECURE DRYER DUCT TO TRUSS WITH APPROVED MATERIAL NOT TAPE 10) ATTACH GARAGE SHEAR TO BLOCKS ( SHEAR TANSFER) 11) NEED WATER TEST 12) MISSING SCREWS IN TRUSS CLIPS 14) SECURE VTRS MAINTAIN PROPER PITCH ON HORIZONTAL VENTS 15) GAS PRESSURE TEST OK 16) DRY WALL NOT SECURED SOFFITS | |
08/07/2001 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) NOT READY FOR INSPECTION |