Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/19/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. |
| 10/18/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*STILL NO CHASE NIPPLE AT ELEC. PENTRATION IN AC UNIT. |
| 10/12/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) A/C UNITS ON ROOF REQUIRE SEPARATE FUSING FOR UNIT & HEAT STRIP. YOU CANNOT RUN THE UNIT & HEAT STRIP OFF OF ONE 60 AMP CIRCUIT. 2.) USE A CHASE NIPPLE WHERE ELEC. WIRES PENETRATE THE HEAT STIP. CABINET. CORRECT & RECALL FOR FINAL. |
| 10/10/2001 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*LABEL DATA PLATES W/PROPER HEAT KIT INSTALLED & FUSE ACCORDINGLY INSTALL CONDENSATE DRAINS ON AIR HANDLERS. |