Permit: T01CM01445

Parcel: 12108067A


Addresses:

6147 E FAIRMOUNT ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/26/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/25/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*GFCI RECEPT OUTSIDE FRONT DOOR DOES NOT TRIP WHEN TESTED UNIT #C.
10/18/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO CLEAR UNITS A & B.
10/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) DISCONNECTS FOR AC UNITS ON ROOF MUST COMPLY WITH 110-26 N.E.C. FOR DEDICATED SPACE. 30" HORIZONAL, 36" IN FRONT.2.) OBTAIN FOR TEMP POWER FOR TESTING AND COMPLETE SIGN OFF SHEET TO RELEASE POWER TO UNITS. 3.) INSTALL PROPER CONNECTORS FOR ROMEX FOR EXHAUST HOODS KITCHEN.4.) INSTALL BOX EXTENDERS FOR OUTLETS INSIDE CABINATES 6.) I.D. CIRCUIT BREAKERS.
09/05/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) NO PLANS/PERMIT 2.) PANEL NOT MADE UP NO BREAKERS