Permit: T01CM01445

Parcel: 12108067A


Addresses:

6147 E FAIRMOUNT ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/10/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
07/03/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) INSTALL FHA OR NAIL PLATES WHERE ROMEX IS 1 1/4" OF STUD FACE TO PREVENT POSSIBLE PUNCHURE OF CABLE, 300-4 N.E.C 2.) PUSH IN PLASTIC BUSHINGS NOT APPROVED FOR ROMEX TERMINATION TO BOX 370-17 N.E.C. 3.) 2 OR MORE GANG BOXES MUST HAVE CRIMP SLEEVE FOR CABLE INTACT, DO NOT BREAK OUT 370-17 N.E.C. 4.) INSTALL BREAKER PANELS AND PANEL FEEDERS.