Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/09/2001 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/05/2001 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) GAS LINE SIZE A. 1" UP FROM GRD AT METER 3/6" ENTERING BLDG. B. GAS LINE UNDER SIZED FOR DEMAND C. GAS LINE UNDER SLAB AND ARIZONA ROOM AT REAR D. WATER HEATER T&P LINE, ARIZONA PLUMBING CODE DOESN'T ALLOW THRU ROOF TERMINATION E> NO PERMIT FOR ELECTRIC UPGRADE, NO INSPECTION |
| 09/17/2001 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) I LOOKED AT THE UNIT ON THE ROOF. I NEED THE CONTRACTOR, OR HOME OWNER TOO BE PRESENT FOR THE NEXT INSPECTION, BECAUSE A. GAS LINE NEEDS TO BE SIZED B. NEED A PRESSURE TEST C. NEED TO INSPECT FOR SIZES AND NUMBER OF GAS APPLIANCES |