Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM01375
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*1.) LABELS MAIN DISCONNECT A& B 2.) INSTALL 2 CIR BREAKER SLOT COVERS WHERE DUCT TAPE IS IN PNL B. | |
07/18/2001 | ELECTRIC - FINAL | Partial Approval | PANELS OK TO CLOSE PLEASE LABEL FINISH PREVIOUS SECTION. | |
07/11/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) DATA CANNOT LAY ON GRID. 2.) EXPOSED M/C CABLE PLEASE PROTECT 3.) NEED TO VERIFY LISTING AND LABELING OF HEAT LAMPS. OK ABOVE CEILING. | |
06/28/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) GAS BOND TO BE ON INTERIOR SIDE OF UNION 2.) CANNOT STACK LUGS NEED FULL SURFACE CONTACT 3.) WILL NEED TO REPLACE PANEL INTERIORS DOE PAINT AND PLASTER ON BUSS SURFACES 110-22 4.) NEED TO OPEN WAL ABOVE PANELS FOR INSPECTIONS ALSO ABOVE SWITCHES IN ALL ROOMS |