Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM01375
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/02/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK WALLS | |
05/22/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1)COMPLETE HOME-RUNS TO PANEL 'A' AND SUPPORT.2)OK ELECTRIC IN BUFFET LINE ONLY. | |
05/20/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1)SUPPORT M/C CABLE AS PER CODE.2)SUPPORT CONDUIT AS PER CODE.3)BOND DEVICE AROUND KNOCKOUTS AT SERVICE.4) TIGHTEN FITTING AT LB. | |
05/09/2001 | ELECTRIC - INTERMEDIATE | Denied | 1) SUPPORT M/C CABLE AS PER CODE 2) SUPPORT CONDUIT AS PER CODE 3) NEED BONDING DEVICE AT CT CAN 250-94 4) NEED SECOND GROUND ROD FOR GROUNDING ELECTRODE SYSTEM |